Battery Backup Calculator

Work out the battery you need for a backup — from the load and the hours — in amp-hours, or see how long a battery you have will last.

A battery is not its label capacity — it is the label times the depth of discharge times the efficiency. This calculator is that honest number, in amp-hours.

Enter the load and the hours; the battery follows.

The total watts of everything the battery must run.
How many hours the backup must last.
The system voltage — commonly 12, 24 or 48 V.
How much of the battery you can use — 80% is a common planning figure. Lead-acid is lower, lithium higher.
Inverter and wiring losses — 90% is a common planning figure.
Enter a battery you have to see how long it lasts at this load.

Formula

energy needed (Wh) = load (W) × backup hours usable battery energy (Wh) = Ah × voltage × depth of discharge × efficiency required Ah = energy needed ÷ (voltage × depth of discharge × efficiency) backup hours from a battery = usable energy ÷ load Defaults: depth of discharge 80%, efficiency 90% — both adjustable.

All lengths are converted to a single unit before the calculation: 1 ft = 0.3048 m, 1 in = 25.4 mm, 1 ft² = 0.09290304 m², 1 yd² = 9 ft². Material quantities are rounded up — you cannot buy part of a tile, plank or bag.

How to use this calculator

  1. Enter the load in watts and the hours you need.
  2. Enter the battery voltage, depth of discharge and efficiency.
  3. Enter a battery capacity to see how long it lasts.
  4. Read the Ah needed — and the backup hours from your battery.

Worked example

Load500 W for 4 hours
Energy500 × 4 = 2,000 Wh
Usable factor80% × 90% = 0.72
Required Ah at 12 V2,000 ÷ (12 × 0.72) = 231.48 Ah
A 200 Ah battery lasts200 × 12 × 0.72 ÷ 500 = 3.46 hours

Check it by hand: every step above uses the formula in the box. If your numbers match the example inputs but the calculator gives a different answer, please report it via the contact page.

Frequently asked questions

What is depth of discharge?

How much of a battery you can use before it is empty. Lead-acid batteries last longer if you only use about 50%; lithium can use 80–90%. Enter your battery's figure.

Why is efficiency less than 100%?

Because the inverter and wiring lose energy — about 10% in a typical system. A 2,000 Wh load needs about 2,222 Wh from the battery before efficiency is counted.

What voltage should I use?

12 V for small systems, 24 V or 48 V for bigger ones — higher voltage means lower current for the same power. Use your system's voltage.

Is this a substitute for electrical design?

No. This is a capacity estimate for planning. Battery, inverter and circuit sizing require qualified professionals and local code compliance — see the safety notice.

Related calculators